NFPA 1989 Standard on Breathing Air Quality for Fire and
Emergency
Services Respiratory Protection
The purpose of the NFPA 1989 is to establish criteria for a safe
supply
of breathing air for emergency services personnel who use
atmosphere-supplying respirators that provide life support during
rescue, confined space operations; hazardous materials operations;
chemical, biological, radiological, and nuclear radiation (CBRN)
terrorism incident operations; and special operations where respiratory
hazards can or do exist.
In 2008, the National Fire Protection Association updated the standard
on "Breathing Air Quality for Emergency Services Respiratory
Protection." This standard is reviewed and revised every 5 years.
We expect a new revision of this standard in 2013.
The NFPA 1989 standard is a copyrighted document so we cannot include
the full text but we have highlighted some of the requirements.
To find this NFPA document, visit www.nfpa.org, and search for NFPA
1989.
NFPA 1989 Specifications:
| Analyte | NFPA 1989 2008 Edition Specification Limits |
| Oxygen | 19.5-23.5% |
| Carbon Monoxide | 5 ppm |
| Carbon Dioxide | 1000 ppm |
| Condensed Oil Mist and Particulate | 2.0 mg/m3 |
| Water | 24 ppm |
| Tota Non-methane Volatile Organic Compounds (VOCs) | 25 ppm |
| Odor | No/slight odor acceptable |
| Nitrogen | 75-81% |
Air Quality Periodic Requirements
Quarterly air analysis of samples shall be tested by an accredited
laboratory and when contamination is suspected.
Air Samples
Air samples shall be taken downstream from purification components and
prior to air storage cylinders. It is acceptable to use a remote
fill hose or air sampling port, if samples are not able to be collected
from inside of the containment fill station.
Special Testing and Procedures for Maintenance Conditions
Air samples shall be collected before and after changing the
purification components or other times when breathing air contamination
could occur, such as, after any alterations, maintenance, repair or
relocation. Passing test results shall be received before
returning the air compressor to service.
Special Testing and Procedures for Contaminated Air
When a sample fails to pass specification, air system must be removed
from service, the cause determined, corrective action taken, retest
performed, and a passing air test received before returning the system
to service.
Compressed Breathing Air Systems
Compressors must be operated for at least 30 minutes each week with two
condensate drain cycles. Air stored in steel cylinders must be
replaced at least annually. The air system intake location must
be acceptable and marked with a placard.
Special Circumstances (See Appendix for suggested procedure)
In the event of an emergency personnel's death, unconsciousness, or
heart attack, the SCBA tank and chain of custody should be submitted to
an accredited laboratory for analysis within 24 hours.
Records
The Emergency service organization shall maintain documentation from
the accredited testing laboratory for 5 years. The accredited
testing laboratory shall maintain documentation for 5 years.
Test Methods
TRI's AIHA accredited Air Testing Laboratory is in full compliance with
the NFPA 1989 Breathing Air Quality for Emergency Services Respiratory
Protection 2008 Edition.


